Art no: 2117

CO2 Mk9 Sensor Add-on KIT

Art no: 2117

Mk9 CO2 Sensor KIT
This complete plug and play KIT can be used to add an additional sensor to an existing LogiCO2 Safety System. The sensor is pre-set to ID2 and receives its power from the existing Safety System. LogiCO2´s Mk9 CO2 Sensor measures the CO2 concentration and alerts in the event that CO2 concentration reaches the pre-set alarm levels. When installed, the system will continuously monitor the CO2 concentration in the room or area where the CO2 sensor is located
It contains a Mk9 CO2 Sensor with display, a Horn/strobe, cabling and signage. Up to twelve sensors can be connected to a LogiCO2 Safety System, providing a sophisticated and powerful CO2 Safety System while still being the most economical and easiest system on the market. All LogiCO2 sensors have automatically calibration as standard. The alarm levels can be changed to any level to comply with all local Safety Codes and legislation.

The pre-set alarm levels are:
– 5000 ppm instantaneous Alert
– 5000 ppm TWA 8Hr (PEL)
– 1,5% (15.000 ppm) ½ STEL
– 3,0% (30.000 ppm) STEL

What is in the package?
CO2 Mk9 detector + Horn/Strobe LED with cable + 10 m power/ communication cable + plug lock + 5m signalization cable + 1 RJ45 1‐1 connector + 1 RJ45 1‐4 connector + manual + H/S sign.

Please note:
A separate installation manual is provided with each extra CO2 sensor kit explaining the simple installation process for adding additional sensors to an existing set.

Specifications

CO2 Sensor MK9
Power supply: 24V DC
Power consumption: No alarm status: 56 mA
Alarm status: Mk9: 68 mA / Mk90: 117 mA
(External optional warning lamp not included)
Wiring connections: RJ 45
Digital interface: RS485 serial port MODBUS
Outputs: 2 x transistor output 24V DC, Min 1 mA
Display: LCD
Acoustic signal-strength: Mk9: 76 dBa / Mk90: 80 dBa (1m) max.
Operating principle: Non-dispersive infrared (NDIR) and thermistor
CO2 measuring range: 0-3 Vol.%
Extended CO2 range: 3-6,7 Vol.%
Gas sampling mode: Diffusion
TWA (Time Weighted Average): Calculation 8 h time span (most recent)
with 2 min sample period. (Pat. Pend.)
Accuracy:
Temperature: ±1°C (±1.8°F)
Resolution: 1°C (1.8°F)
Annual zero point drift: <0.01 Vol.% with automatic self calibration feature
Operating temperature range: 0 to +45°C (32 to +113°F). Only for indoor use.
General performance
Compliance with: 2004/108/EG Sensor Life expectancy: > 15 years
Operating humidity range: 0 to 95% RH (non condensing)
Warm-up time (@ 22°C): 1 min.
Dimensions (LxWxD): 90 x 161 x 38 mm / 3.5” x 6.3” x 1.5”
Ingress protection: IP56
Overvoltage: Category II
Pollution degree: II