Art no: 2049

What is in the package?

CO2 Sensor Mk9

Art no: 1134

Central Unit Mk9

Art no: 1148

Horn/Strobe LED amber glass

Art no: 0440

Power Supply 1A

Art no: 0021

CO2 Mk9 Detector Base SET

Art no: 2049

MK9 CO2 Safety system
The Mk9 CO2 sensor is the latest generation of CO2 Safety Systems and has replaced the LogiCO2 MkVII CO2 Sensor System. A large display, functional design and revolutionary language functionalities are some of the new features of the MK9 CO2 Safety System. The display alternates between actual CO2 concentration (0.0%- 6,7%), TWA (ppm) and temperature (°C or°F), (if temperature alarm is activated for cold room applications).

This complete plug and play SET contains a Mk9 CO2 Sensor with display, a Mk9 Central Unit to display the measured values, a Horn/strobe, cabling and signage. Up to twelve sensors can be connected to the Mk9 CO2 Safety Detector SET, providing a sophisticated and powerful CO2 Safety System while still being the most economical and easiest system on the market. All LogiCO2 sensors have automatically calibration as standard. The alarm levels can be changed to any level to comply with all local Safety Codes and legislation.

The default alarm levels are:
– 5.000 ppm Awareness Alert
– 5000 ppm TWA 8Hr (PEL)
– 1,5% (15.000 ppm) ½ STEL
– 3,0% (30.000 ppm) STEL

The CO2 Mk9 Detector SET is available in the following languages:
Chinese Simplified
Danish
Dutch / Netherlands
English
Filipino
Finnish
French
German
Hebrew
Indonesian
Italian
Japanese
Korean
Norwegian
Polish
Portuguese
Portuguese Brazilian
Russian
Spanish
Swedish
Thai

The Asian version also has:
– Chinese Simplified
– Thai
– Japanese
– Korean

What is in the package?
CO2 Mk9 detector + Central Unit Mk9 + Horn/Strobe LED incl. cable + 10 m power/ communication cable + power supply incl. cable + plug lock + 5m signalization cable + 1 J45 1‐1 connector + 1 RJ45 1‐2 connector + manual + Central Unit sign+ H/S sign and collar seals.

What is in the package?

CO2 Sensor Mk9

Art no: 1134

Central Unit Mk9

Art no: 1148

Horn/Strobe LED amber glass

Art no: 0440

Power Supply 1A

Art no: 0021
Specifications
Mk9 CO2 Sensor, Specifications
Power consumption:
No alarm status: 56 mA. Alarm status: 68 mA (external optional warning lamp not included)
Wiring connections:
RJ 45
Digital interface:
RS485 serial port MODBUS
Outputs:
2 x transistor output 24V DC, Min 1 mA
Display:
LCD
Acoustic signal-strength:
76 dBa (1m) max.
Approval:
Manufactured in accordance with DIN 6653-2.
The CO2 Safety System is tested and approved by the German TÜV-Rheinland.
EN 50081-1 / EN 50082-2 /CE.
Certified by UL.
Operating principle:
Non-dispersive infrared (NDIR) and thermistor
CO2 measuring range:
0-3 Vol.%
Extended CO2 range:
3-6,7 Vol.%
Gas sampling mode:
Diffusion
TWA (Time Weighted Average):
Calculation 8 h time span (most recent) with 2 min sample period. (Pat. Pend.)
Accuracy
Temperature:
±1°C (±1.8°F)
Resolution:
1°C (1.8°F)
CO2:
±5% of measured value plus a pressure dependence of +1.6% of reading per kPa/0.295 InHg at 0-40°C (32-102°F).
Resolution:
0.01 Vol.%
Annual zero point drift:
<0.01 Vol.% with automatic self calibration feature
Ambient temperature:
-20 to +50°C (-4 to +122°F). Only for indoor use.
General performance
Compliance with:
2004/108/EG Sensor
Life expectancy:
> 15 years
Operating humidity range:
0 to 95% RH (non condensing)
Warm-up time (@ 22°C):
1 min.
Dimensions (LxWxD):
90 x 161 x 38 mm / 3.5” x 6.3” x 1.5”
Ingress protection:
IP54 according to TÜV, IP44 according to UL
Overvoltage:
Category II
Pollution degree:
II
Manuals & instructions
English
English
Other languages
Russian
Portuguese (Portugal)
Polish
Japanese
Italian
German
Dutch
Chinese (Simplified)
French
Spanish
Swedish
Thai

Mk9 tutorial (English)

Mk9 tutorial (Spanish)

Mk9 tutorial (German)

Mk9 tutorial (French)

Mk9 tutorial (Chinese)

Software